584SV 0.75 to 355kW |
 |
 |
User Benefits |
 |
Totally programmable control block diagram |
 |
High torque sensorless vector control with auto-tune |
 |
User selectable constant or quadratic (fan law) torque |
 |
Local or remote operator controls |
 |
Multi lingual programming |
 |
Panel or direct wall mount
|
The totally programmable block diagram of the 584SV inverter makes it ideal for the simplest to the most complex applications. Each function block can be simply interlinked to any other to provide the exact control strategy required. The 584SV also provides sensorless vector high torque performance with the convenience of rapid auto-tuning.
Features: Man Machine Interface
32 character plain language display
Selectable English, French, German or Code
Wide viewing angle back-lit LCD
Logical menu structure programming
Local control of forward/reverse, run/stop, jog
Selectable first-up diagnostic readout
Health, run, brake, local LED identification
Password and function lock-out security
User Facilities
Programmable block diagram
Sensorless vector with auto-tune control
Constant or quadratic (fan law) torque rating
Up to 16 motor stored configurations
Panel or direct wall mounting
Linear, parabolic or (S) ramp
Spinning load (flycatching) controlled start
Selectable auto restart after trip
Trip history
Multiple programmable stopping modes
On board process PID control
On board raise/lower ramp (digital MOP)
Low or high voltage supplies
4 skip frequencies
Slip compensation
8 preset speeds
Hoist/lift automatic brake control
HVAC and 584S Macro configurations
|
TECHNICAL SPECIFICATION
Inputs/Outputs:
Analogue Inputs:3 configurable ( 0-10V, 0+10V, 0-20mA, 4-20mA, 20-0mA or 20-4mA)
Default: Speed setpoint; speed trim; remote setpoint
Analogue Outputs:2 configurable ( 0-10V, 0+10V, 0-20mA, 4-20mA, 20-0mA or 20-4mA)
Default: Output frequency; load
Digital Inputs: 8 configurable (24V)
Default: Run; ast ramp; direction; external trip; jog; preset 1; preset 2; manual/auto select
Digital Outputs: 3 configurable (relay contact)
Default: Health; zero speed; at speed
Protection:
Short circuit phase-phase
Short circuit phase-earth
Current limit 50 - 150% (programmable)
Shock load limit 180% Overcurrent >220%
I x t overload 50 - 150% (programmable)
Heatsink overtemperature Motor thermistor overtemperature
Overvoltage Undervoltage
Power Supply:
380 - 460V ± 10% 50 - 60Hz (three phase) or
208 - 240V ± 10% 50 - 60Hz (three phase)
Ambient:
0 - 50 °C (0 - 40 °C with top cover fitted)
up to 1000m ASL without derating (Package size 4-7)
0 - 40 °C up to 1000m ASL without derating (Package size 8-10)
Overload:
150% for 60 seconds (constant torque) 110% for 10 seconds (quadratic torque)
Output Frequency:
0 - 120/240/480Hz (Programmable) (Package size 4-7) 0 - 120Hz (Package size 8-10)
Switching Frequency:
3/6/9kHz (Package size 4)
3/6 kHz (Package size 5,6,7)
3kHz (Package size 8,9,10)
(All with audibly silent switching pattern)
Standards:
CE marked.
EN50081-1(1992) (EMC emissions, light industrail with internal filters fitted - sizes 4-7).
EN50081-2(1992) (EMC emissions, heavy industrial with internal filters fitted - sizes 8-10).
pr EN50082-2(1992) (EMC immunity, heavy industrial).
VDE 0160(1994) /pr EN50178(1995) (Safety, low voltage)
UL and cUL designated and submitted.
|